Load Characteristic Model: LDVFD_A
Following corrections are automatically when using LDVFD_A when simulating.
- For parameters Tv, T1, and T2
If T < 4*TimeStep then T = 4*TimeStep
TimeStep represents the integration time step being used as described on TimeStep
Model Equations and/or Block Diagrams
Parameters:
| K1 | Washout gain for active power (pu) |
| T1 | Time Constant for active power (seconds) |
| K2 | Washout gain for reactive power (pu) |
| T2 | Time Constant for reactive power (seconds) |
| Pmax | Maximum value of active power (as a multiple of the initial MW output) |
| Qmax | Maximum value of reactive power (as a multiple of the initial Mvar output) |
| V0 | voltage break-point for low voltage cut-out of the inverter (Multiplier = 0.0 at this voltage) |
| V1 | voltage break-point for low voltage cut-out of the inverter (Multiplier = 1.0 at this voltage) |
| Tv0 | voltage break-point for low voltage cut-out timer (If voltage stays below vl0 for more than tvl0 seconds, then the multiplier will remain zero for the simulation) |
| Tv1 | voltage break-point for low voltage cut-out timer (If voltage stays below vl1 for more than tvl1 seconds, then the multiplier will track a depressed curve according to Vrfrac and an internally tracked value of the minimum voltage experienced during the simulation) |
| Vrfrac | fraction of device that recovers after voltage comes back to within vl1 < V < vh1 (Note that the timers Tvl1 also impact when this fraction is used) |
| Tv | time constant on the output of the voltage cut-out |
| Pfinit | Initial power factor (used when part of a CompLoad) |